๐Ÿ‘‹ Introduction

A pad footing must be checked against bearing capacity to ensure the ground under it is not overstressed:

  • Applied pressure: The vertical force and the moment are transferred to the soil as a pressure under the base.
  • Soil capacity: The soil can only carry an allowable pressure before it fails in shear or settles too much.
Footing pressing into soil with applied pressure exceeding safe soil bearing capacity Two panels. Left: a footing carrying a vertical load, with the resulting contact pressure q compared against the soil's safe bearing capacity on a simple bar comparison. Right: the footing has sunk and tilted from its original dashed position, because the applied pressure exceeded the safe bearing capacity, causing uneven settlement. 1. Applied pressure vs. capacity V q = contact pressure Soil holds steady while qallow โ‰ฅ q 2. If bearing failure occurs V sinks Footing sinks and tilts unevenly when q > qallow


This work example runs the bearing stress check of a 3.0 m ร— 3.0 m pad footing, 1.0 m deep, carrying a vertical force Fx = 20 + 5 kN and an applied moment My = 50 + 50 kNm, in the same order a calculation report runs it:

  1. Base geometry โ€” the area, the second moment of area and the distance to the edge
  2. Load combination โ€” the vertical force and moment at service level (SLS)
  3. Self weight โ€” the weight of the footing pressing into the ground
  4. Bearing stress โ€” the maximum and the minimum pressure under the base

The footing in this example also carries a horizontal force Fy = 50 + 10 kN at the base, but that force is a sliding problem, not a bearing problem โ€” it is checked separately in the sliding work example.

The concept behind each step is explained in the companion article: Pad Footing Stability Check: Sliding, Overturning and Bearing Capacity - A Simple Guide.

๐Ÿ“ Design Data

Below is the design information of the pad footing, which we will check under the vertical force and the applied moment.

Pad Footing
Type Pad footing (concrete)
Length, L 3.0 m
Width, W 3.0 m
Depth, D 1.0 m
Design Loads
Vertical Force, Fx (Dead / Live) 20 kN / 5 kN
Horizontal Force, Fy (Dead / Live) 50 kN / 10 kN
Applied Moment, My (Dead / Live) 50 kNm / 50 kNm
Soil
Allowable Bearing Pressure, qallow 250 kPa
Material
Concrete Density, ฯ 25 kN/mยณ
Load Combination (SLS)
Dead Load Factor, fDL 1.0
Live Load Factor, fLL 1.0


3.00 m 3.00 m Fig. 1 Rectangular Area

๐Ÿ”ข Calculation Steps

*The check below follows the code-neutral factor-of-safety practice of the stability check guide.

1.Geometry

Base Area
=
=
=
Second Moment of Area of the Base
=
=
=
Distance from the Neutral Axis to the Edge
=
=
=

2.Load Combination (SLS)

Vertical Force (service)
=
=
=
Applied Moment (service)
=
=
=

3.Footing Self Weight

*The footing has its own weight, and that weight presses down on the soil exactly like the column load does. It is a dead action, so it is carried with the dead load factor fDL.
Footing Volume(Geometry)
=
=
=
Footing Self Weight(Concrete density ฯ = 25 kN/mยณ)
=
=
=

4.Bearing Stress

3.00 m F = 25 kN M = 100 kNm Fig. 2 Pad Footing - For Bearing Stress
Stress
=
=
=
50 kPa 5.56 kPa Fig. 3 Stress Block Analysis
Max. Bearing Stress
>
>
checking of max. bearing stress pass, ok!
Min. Bearing Stress
>
>
checking of min. bearing stress pass, ok!

โˆด The section is sufficient for Bearing Capacity.

๐Ÿ“‹ Summary

Checking Item Current Allowable Utilization Pass?
Maximum Bearing Stress 50 kPa 250 kPa 20% Pass
Minimum Bearing Stress 5.56 kPa > 0 N/A Pass
Overall Pass
The Pad Footing (3.0 m ร— 3.0 m ร— 1.0 m) is sufficient under Fx = 20 + 5 kN, Fy = 50 + 10 kN and My = 50 + 50 kNm, it :
โœ“ Maximum Bearing Stress Check (util: 20%)
โœ“ Minimum Bearing Stress Check (5.56 kPa > 0)

๐Ÿ™‹ Frequently asked questions

1. What is the bearing stress check of a pad footing?

It confirms that the pressure under the base stays within what the soil can carry. The maximum bearing stress must not exceed the allowable bearing pressure (50 kPa against 250 kPa here), and the minimum bearing stress must stay positive so that no part of the base lifts off (5.56 kPa here).

2. Why is the self weight included in the bearing pressure?

Because the footing's own weight is a real load on the soil โ€” the 1.0 m deep footing weighs 225 kN, which is 90% of the 250 kN pressing on the base. Leaving it out would understate the pressure and can under-size the footing.

3. Why must the minimum bearing stress stay positive?

Because the moment can push the pressure so hard onto one edge that the other edge lifts off, giving a negative minimum stress. Once tension appears under the base, the linear stress formula no longer applies and the pressure has to be recalculated on the reduced contact area.

4. Which load combination is used for the bearing check?

Here the service level combination (1.0 ร— dead + 1.0 ร— live) is used, because the allowable bearing pressure from the soil investigation is a service level value. Some codes work with factored ULS loads against a design bearing resistance instead โ€” check which convention your design code uses, and use it consistently.

5. What is the middle third rule and how is it related to this check?

It is the same check in another form: the resultant of the vertical force must fall within the middle third of the base, e โ‰ค B/6. Here e = M/N = 100/250 = 0.40 m against B/6 = 0.5 m, so the base is fully in compression โ€” exactly what a positive minimum stress tells us.

6. What can I do if the bearing check fails?

Widen the base โ€” a larger area and a smaller bending term at the same time. Deepen the footing for more self weight (it must be founded in competent material), improve the ground (compacted granular layer, ground improvement, piles), or reduce the moment by bracing the column. The bending term Mยทy/I falls with the square of the base width, so widening is very effective.

๐Ÿ“„ Need a Pad Footing Bearing Stress Check in Your Design Report?

If you want a ready-to-submit design report with the bearing stress check and the full stability checks of your pad footing, feel free to try our application โ€” what you need is just the design data values, and a ready-to-submit PDF report will be generated in a minute.